A deep leg metal track accommodates vertical movement of the metal stud wall beneath the bottom of the structure, maintaining a one-and-one-half-inch clearance. The track is secured with three-sixteenth-inch diameter by one-and-one-eighth-inch minimum embedment drilled anchors spaced at twenty-four inches on center with a maximum of six inches from the ends. Bridging is installed as noted per detail G on the same sheet. Fire barrier sealant is applied on both sides at rated partitions.
1 1/2" DETAIL G (THIS SHEET) BRIDGING AS NOTED ON SIDES AT RATED PARTITIONS FIRE BARRIER SEALANT BOTH DRILLED ANCHORS @ 24" O.C. 3/16" ∅ x 1 1/8" MIN EMBED DEEP LEG MET TRACK w/ FREE TO MOVE VERTICALLY & MAX 6" FROM ENDS MET STUD AND TRACK BOTTOM OF STRUCTURE IN DEEP LEG TRACK METAL STUD TOP TRACK