A laboratory analyzer with a maximum operating weight of 120 pounds and a center of gravity located 37 inches above the floor slab is secured to a concrete slab on grade using an L 2 1/2 x 2 1/2 x 14 gauge cold-formed steel angle fastened with four 1/2-inch diameter Hilti KB-TZ2 expansion anchors providing 3 1/4 inches of effective embedment per ESR-4266, along with two number 12 sheet metal screws. The assembly restrains the equipment against overturning forces while transferring loads directly into the floor slab.
CG 2'-0" MIN CG MAX OPER WT = 120# L2 1/2x2 1/2x14GA W/ (4) 1/2" DIA HILTI KB-TZ2 W/ 3 1/4" EFF EMBED (ESR-4266) & (2) #12 SMS 37" CONC SLAB ON GRADE