This detail specifies the required square opening dimensions for circular pipe penetrations through metal decking. The schedule dictates that a 4-inch diameter pipe requires a 12-inch square opening, an 8-inch diameter pipe requires a 24-inch square opening, and a 12-inch diameter pipe requires a 36-inch square opening. The assembly shows the pipe passing through the metal deck profile with a surrounding square cutout.