A buffer tank with a maximum operating weight of 3650 pounds and a center of gravity height of three feet above the concrete pad is secured using one-half-inch diameter stainless steel Simpson Strong-Bolt 2 anchors passing through mounting holes in the rail or plate per manufacturer specifications. The anchors require a two-and-one-half-inch embedment depth into the concrete. A minimum distance of eight inches must be maintained from the center of any anchor to the edge of the slab or construction joint.
BUFFER TANK, MAX OPERATING WT = 3650 LBS, MAX HT ABV CONC PAD TO CTR OF GRAVITY = 3'-0" 1/2"Ø SS SIMPSON STRONG-BOLT 2 THROUGH HOLE IN RAIL OR PL PER MFR W 2 1/2" EMBED NOTE: MIN DISTANCE FROM CENTER OF ANCHOR TO EDGE OF SLAB OR CONSTRUCTION JOINT = 8".
Members view this detail in full resolution, download the CAD files (SVG, PDF), and can adapt it in the built-in CAD editor — export DXF, DWG, or PDF.