A non-bearing cold-formed metal stud wall framing assembly extends between concrete slabs or metal decks. The metal studs are spaced at sixteen inches on center and require bridging at forty-eight inches on center where gypsum board is omitted from either surface. Height limitations based on stud gauge and size are included, along with a complete fastener schedule specifying approved anchors, screws, and spacing.
3/4" "H" METAL STUD WALL SECTION B A STUD PARALLEL TO STEEL NOTES: 1. MAXIMUM STUD HEIGHT "H" FOR STUDS @ 16" OC. 2. SEE ARCHITECTURAL FOR OTHER CONDITIONS. 3. LIMIT L/240 DEFLECTION. 4. STUDS CARRYING EQUIPMENT OR CASEWORK WEIGHING 40 LBS OR MORE SHALL BE 16GA MIN. EA SIDE EA STUD MTL STUD @ 16"OC, UNO, PER TABLE BLW. PROVIDE BRIDGING @ 48"OC WHERE GYPSUM BOARD IS NOT APPLIED TO BOTH SURFACES. T.O. SLAB MAX HEIGHT NON-BEARING NEW STUDS GA (MILS) METAL STUD SIZE (1 3/8" FLANGE) 362 400 600 800 19'-4" 21'-6" 29'-11" 38'-1" 18'-1" 20'-1" 27'-11" 35'-6" 16'-11" 18'-9" 26'-0" 33'-1" 15'-6" 17'-3" 23'-11" - 6 5 4 3 2 1 HILTI KB-TZ 1/4"Øx2" EMBED EXPANSION ANCHOR @ 12"OC HILTI DNI32 P8 PDF @ DECK W/ CONC OR #10 SMS @ ROOF MTL DECK HILTI DNI32 P8 PDF @ 16"OC HILTI DNI32 P8 PDF @ 16"OC #10 SHEET METAL SCREW (SMS) #12 SMS FASTENER SIZE & SPACING MARK REMARKS ESR-1663 ESR-1663 ESR-1663 ER-5202 ER-5202 ER-1917 METAL STUD FASTENER SCHEDULE 14 (68) 16 (54) 18 (43) 20 (33)