An engine generator operating at 480V with a switching neutral downstream connects to a circuit breaker in the general distribution panelboard. Ground connections to the enclosure require a minimum number six conductor. A number four-slash-zero grounding electrode conductor extends from the neutral. Ground lugs mounted to the case of the engine generator must attach to a solid area of the case to ensure full contact. A number four-slash-zero grounding connection links the engine generator chassis and the electrical equipment shelter via an exothermic weld. A factory-provided main bonding jumper is sized per National Electrical Code table 250.102(C)(1).
A. GROUND CONNECTIONS TO THE ENCLOSURE MUST BE MINIMUM #6. ENGINE GENERATOR OPERATING AT 480V WITH SWITCHING NEUTRAL DOWNSTREAM GROUND G A B C TO E/G CIRCUIT BREAKER IN GDPH NEUTRAL 1. #4/0 GROUNDING ELECTRODE CONDUCTOR. 2. GROUND LUG(S) MOUNTED TO CASE OF ENGINE GENERATOR MUST BE MOUNTED TO SOLID AREA OF CASE SO THAT GROUND LUG(S) MAKES FULL CONTACT WITH CASE. 3. PROVIDE #4/0 GROUNDING CONNECTION BETWEEN THE E/G CHASSIS AND THE EES VIA EXOTHERMIC WELD. 4. FACTORY-PROVIDED MAIN BONDING JUMPER, SIZED PER NEC TABLE 250.102(C)(1). KEYED NOTES: GENERAL NOTES: 1 2 3 4 E D