An insulated carrier pipe is suspended from overhead using an adjustable clevis hanger. Rigid pipe insulation is installed directly at the support point to prevent crushing of the thermal insulation. A twenty-two gauge sheet metal insulation shield, eighteen inches long, wraps the lower section of the insulation within the clevis loop to distribute the load and protect the jacket.
PIPE INSULATION RIGID INSULTION AT SUPPORT 22 GAUGE SHEET METAL INSULATION SHIELD - 18" LONG CLEVIS HANGER CARRIER PIPE