Medium pressure gas piping enters from the supply line through an isolation valve and a three-inch minimum dirt leg. An Eaton Model 85 strainer is provided ahead of the pressure-reducing valve when using a ventless PRV. Unions are installed on both sides of the valve for maintenance if the assembly is not flanged. A Pete's plug provides pressure testing access before the gas continues downstream to equipment.
ISOLATION VALVE PROVIDE EATON MODEL 85 STRAINER IF VENTLESS PRV PETE'S PLUG PRESSURE REDUCING VALVE DIRT LEG, 3" MIN UNION (IF NOT FLANGED) PRV X NG TO EQUIPMENT SEE P5.30 MPG
Members view this detail in full resolution, download the CAD files (SVG, PDF), and can adapt it in the built-in CAD editor — export DXF, DWG, or PDF.