Hot water supply and return lines connect to a heating coil through service valves, unions, a strainer, a Pete's plug, and a 2-way auto valve. Flexible pipe connections interface with the coil unit at full line size. An automatic air vent sits at the high point of the piping, and a 3/4-inch ball valve with a hose adaptor is installed for drainage. Unions are positioned to permit removing the coil without dismantling the header.
AUTOMATIC AIR VENT AT HIGH POINT AIR FLOW 3/4" BALL WITH HOSE ADAPTOR 2-WAY AUTO VALVE SERVICE VALVES HWS HWR FULL LINE SIZE NOTES: 1. LOCATE UNION TO PERMIT REMOVING COIL WITHOUT DISMANTLING HEADER. STRAINER PETE'S PLUG PIPE FLEXIBLE CONNECTION (TYP.)