A 1350-pound boiler unit mounts onto a four-inch concrete pad resting on the floor. The boiler tubing frame is anchored using four field-supplied two-by-two-by-three-eighths-inch angle clips measuring two and one-half inches long on both sides. Each angle clip is secured to the concrete pad with a three-eighth-inch diameter Hilti KB-TZ expansion anchor having a two-and-three-quarter-inch embedment depth. Clips and welds are covered with a protective coating to prevent rust.
PER 11/S3.01 FLOOR FIELD SUPPLIED 2"x2"x3/8"x2-1/2" LONG ANGLE CLIP (TYP OF 4) BOTH SIDES ANGLE TO BOILER TUBING FRAME ATTACH TO CONCRETE PAD WITH 3/8" DIA HILTI KB-TZ, 2-3/4" EMBEDMENT (TYP OF 4) COVER CLIPS AND WELDS WITH PROTECTIVE COATING TO PREVENT RUST. 1350 LBS CONCRETE PAD SEE QA NOTES ON S0.10 (TYP) 4" 65-3/4" 34-1/2" 55" 57-3/8" 32-3/4"