The condensate drain trap is piped using Type M copper tubing connected to the air conditioning unit drain pan through a casing sleeve, a reducer, and a union. A drain plug is provided at the bottom of the trap. The vertical drop dimensions A and B are determined by the fan static pressure and unit tonnage formulas shown. The downstream piping includes a vent open to the atmosphere and discharges condensate into a roof drain with a minimum slope of 1/8 inch per foot.
DISCHARGE CONDENSATE INTO ROOF DRAIN. MIN. SLOPE 1/8" PER FOOT VENT OPEN TO ATMOSPHERE CASING SLEEVE UNION TYPE "M" COPPER TUBING DRAIN PLUG DRAIN PAN A = B + 1/2 FAN STATIC PRESSURE B = 1" (1" UP TO 40 TONS) B A A REDUCER AS NECESSARY = 1-1/4" (UP TO 90 TONS)