Turning vanes are installed inside rectangular duct elbows to guide airflow smoothly around 90-degree turns. The vane spacing is calculated as one-sixth of the duct dimension with a minimum spacing of two inches. The number of spaces is determined by dividing the duct width by the vane spacing. Vane radius is set to one and a quarter times the spacing, and the trailing edge extension is three-quarters of the spacing.
S S S S L L W W D S= D/6 (MIN.2") W/S= NO. OF SPACES R= 1 1/4 S L= 3/4 S
Members view this detail in full resolution, download the CAD files (SVG, PDF), and can adapt it in the built-in CAD editor — export DXF, DWG, or PDF.