An expansion tank rests on a nominal three-and-a-half-inch concrete pad provided by the general contractor and reinforced with a single layer of number four reinforcing bars at twelve-inch centers both ways. Five-eighth-inch stud wedge anchors secure the perimeter at twenty-four-inch centers and the interior at thirty-six-inch centers. The make-up water line from the domestic system connects to the hydronic system through a strainer, backflow preventer, pressure reducing valve when required, zero to sixty psi pressure gauge, and typical ball valves. A dielectric nipple connects the main service pipe with a normally open ball valve and a minimum six-inch thermal trap on hot services.
ET-X FLOOR (BY OTHERS) MINIMUM 6" THERMAL TRAP ON HOT SERVICES MAIN SERVICE PIPE NORMALLY OPEN BALL VALVE MAKE-UP WATER FROM DOMESTIC SYSTEM SEE PLANS FOR SIZE TO HYDRONIC SYSTEM STRAINER BACKFLOW PREVENTER PRV (WHEN REQUIRED) 0-60 PSI PRESSURE GAUGE (SEE SCHEDULE) BALL VALVE (TYPICAL) NOMINAL 3 1/2" CONCRETE PAD BY GENERAL CONTRACTOR WITH (1) LAYER OF #4 REBAR AT 12" CENTERS BOTH WAYS AND 5/8" SAS STUD WEDGE ANCHORS AT 24" CENTERS AT PERIMETER AND 36" CENTERS AT INTERIOR (TYPICAL) EXPANSION TANK DIELECTRIC NIPPLE