An inline axial fan is mounted on two-inch spring isolators resting upon a six-inch concrete pad installed by the general contractor. The fan features a top-mounted belt-drive open drip-proof motor and a factory bell mouth with an inlet guard. The discharge side connects to a canvas flex connection leading to a sheet metal exhaust plenum rated for one hundred seventy degrees Fahrenheit. A backdraft damper is integrated into the exhaust transition.
6" CONCRETE PAD BY G.C. 2" SPRING ISOLATORS CANVAS FLEX TO SHEET METAL EXHAUST PLENUM RATED FOR 170F FACTORY BELL MOUNT WITH INLET GUARD BACKDRAFT DAMPER BELT-DRIVE ODP MOTOR ON TOP