An evaporative cooling unit features a 12-inch sump with a bottom sloped to one end by the equipment manufacturer. Six-inch distribution headers supply water with 3/4-inch holes drilled at regular intervals. A pump provided by the manufacturer connects to the sump alongside a 3-inch outlet drain and a 3-inch overflow drain with a trap and roof interceptor. Associated mechanical and plumbing lines include a 12-inch bypass with motorized dampers, Belimo motorized valves programmed by automatic temperature controls for drain and flush cycles, a float valve, a biocide tablet holder, a pressure-reducing valve, and a backflow preventer.
ECC-1 KEYED NOTES ECC-1 1 DRAIN 3" OUTLET 2\" 3" OVERFLOW DRAIN W/ TRAP ROOF INTERCEPTOR 1 5 4 \" 1" 1" 1" 1" 3/4" 3/4" 1" 2 1 MANUFACTURER) (PROVIDED BY PUMP 6" DIST. HEADER 6" DIST. HEADER 12" SUMP 3/4" HOLED DRILLED AT 6" 3 5 4 3 2 1 5 6 PROVIDE BOLEMO MOTORIZED VALVES TO BE PROGRAMMED BY ATC FROM DRAIN AND FLUSH CYCLE. FLOAT VALVE BIOCIDE TABLET HOLDER. PRV VALVE BY PLUMBING CONTRACTOR FLOOR (BOTTOM) OF SUMP TO BE SLOPED TO ONE END BY EQUIPMENT MANUFACTURER. PROVIDE _" PER FOOT SLOPE. BACKFLOW PREVENTER BY PLUMBING CONTRACTOR. M 12" BYPASS BY PLUMBING CONTRACTOR BY MANUFACTURER WITH MOTORIZED DAMPERS