The condensing unit sits on a concrete pad supported by the roof structure. A three-quarter-inch Mason Industries Super W neoprene waffle pad isolates vibration beneath each leg. Half-inch diameter Hilti KB-TZ stainless steel expansion anchors with three-inch embedment secure the unit at each leg. Maintenance clearances require eighteen inches minimum for coil side and rear access, and thirty-six inches for front and side access per manufacturer specifications.
NOTES ROOF. CONCRETE PAD. 3/4" MASON INDUSTRIES SUPER W NEOPRENE WAFFLE PAD. PROVIDE 18" MINIMUM CLEARANCE FOR COIL SIDE AND COIL REAR. PROVIDE 36" CLEARANCE FOR FRONT AND SIDE ACCESS AND 18" FOR LEFT AND REAR ACCESS. REFER TO MANUFACTURER'S WRITTEN SPECIFICATIONS FOR DETAILS. 1 2 3 4 5 1/2"Ø HILTI KB-TZ EXPANSION ANCHORS (STAINLESS STEEL, ESR-1917) WITH 3" EMBEDMENT AT EACH LEG. CU - 5 4 3 1 2