Cold-formed steel horizontal and vertical metal studs connect to a wide-flange structural beam sized per plan using a two-inch by six-inch maximum, sixteen-gauge bent plate at each horizontal metal stud. The bent plate welds to the underside of the structural beam flange with a one-eighth-inch fillet weld of two-inch length typically, maintaining a half-inch maximum clearance typical. Two number-ten sheet metal screws fasten the horizontal studs to the bent plate with a two-inch minimum and six-inch maximum dimension.
Wx BEAM PER PLAN BENT PL 2"x6" MAX x 16 GA @ EA HORIZ METAL STUD (2) #10 SMS VERT STUDS 1/8 2" TYP TYP 1/2" MAX 6" Wx BEAM PER PLAN (2) #10 SMS MAX 6" MIN 2" HORIZ STUDS MIN 2"