A hollow structural section beam sized per plan connects to an exterior cold-formed steel stud wall using a one-quarter-inch continuous bent plate welded with three-sixteenths welds. The cold-formed steel stud utilizes a TSN Verticlip SLB fastened with all slots filled per the manufacturer recommendations, maintaining a three-quarter-inch maximum gap. Utility punches must be located a minimum of ten inches away from the connection. A note specifies that one row of bridging shall be located a maximum of twelve inches from the clip typically.
LOCATE UTILITY PUNCH AWAY FROM CONN., 10" MIN. HSS BEAM SEE PLAN TSN VERTICLIP SLB, FILL ALL SLOTS, PROVIDE FASTENERS PER MANUFACTURER GAP 3/4" MAX SAD GRID LINE OR C L 1/4" CONT. BENT PLATE 3/16 2/6 3/16 2-6 NOTE: ONE ROW OF BRIDGING SHALL BE LOCATED A MAX OF 12" FROM CLIP, TYP 2 LO S1.4.8