An air sampling smoke detector apparatus and power supply are mounted to the wall above the floor slab at a height ranging from four feet minimum to five feet maximum. Rigid three-quarter-inch CPVC pipe connects to the inlet manifold, noting that adapters or pipes must not be glued directly into the manifold. Each sampling pipe includes a cleanout port equipped with an air hose quick disconnect connection and an upstream ball valve for isolation. A Unistrut channel supports the piping runs, maintaining a twenty-inch minimum clearance before any bends. Pipe labeling is required for identification.
FLOOR SLAB RIGID 3/4" CPVC PIPE ONLY DO NOT GLUE ADAPTER OR PIPE DIRECTLY INTO INLET MANIFOLD 2 POWER SUPPLY AIR SAMPLING SMOKE DETECTOR APPARATUS. UNISTRUT MOUNTED TO WALL. 4'-0" MIN 5'-0" MAX 1 1 2 20" MIN BEFORE BENDS EF001 1 PIPE LABEL PROVIDE CLEANOUT PORT FOR EACH ASSD PIPE. CLEANOUT PORT SHALL BE PROVIDED WITH AN AIR HOSE QUICK DISCONNECT CONNECTION AND AN UPSTREAM BALL VALVE TO ISOLATE ASSD PIPING FROM DETECTOR.