An early suppression fast-response sprinkler pipe is positioned with its head typical at zero feet eight inches below the deck to the center of the pipe, maintaining a twelve-inch minimum clearance from structural bridging and adjacent conduit or pipe. A three-foot-zero-inch by two-foot-zero-inch clear space zone is maintained around the sprinkler head to prevent spray pattern obstructions.
G R E G J ON E S B Y ---- \ B U I L D I NG F \ T I TLE B L O C K . DGN 12" MIN. 12" MIN. BRIDGING STRUCTURAL TO CENTER OF PIPE @ 0’-8" BELOW DECK WITH HEAD TYPICAL SPRINKLER PIPE PIPE CONDUIT OR O F P I P E C E N TE R L I N E 8 " 3 ’ - 0 " SP A C E C LE A R 2’ - 0"