An ESFR sprinkler pipe with head is positioned eight inches below the deck to the center of the pipe. Structural bridging is located twelve inches minimum from the sprinkler pipe. Conduit or pipe obstructions maintain a three-foot clear space height by two-foot width relative to the sprinkler head.
12" MIN. 12" MIN. BRIDGING STRUCTURAL TO CENTER OF PIPE @ 0’-8" BELOW DECK WITH HEAD TYPICAL SPRINKLER PIPE PIPE CONDUIT OR O F P I P E C E N TE R L I N E 8 " 3 ’ - 0 " SP A C E C LE A R 2’ - 0"