An eight-by-eight-by-six-inch square junction box is mounted above the door in the ceiling space of the secure side, receiving a one-hundred-twenty-volt emergency power connection and routing to a door latch power supply. Three-quarter-inch conduits run from the junction box to a power transfer at the door hinge and to a surface-mounted proximity card reader on the unsecure side set at forty-two inches above finished floor. An additional one-inch conduit extends from the junction box to the door controller cabinet. The electric fire exit hardware on the exterior side connects directly into the low-voltage power transfer loop.
1' CONDUIT TO DOOR CONTROLLER CABINET 3/4" C. DOOR LATCH POWER SUPPLY 3/4" C. +42" A.F.F. PROXIMITY CARD READER, SURFACE MOUNTED ON THE UNSECURE SIDE. 8"X8"X6" SQ JUNCTION BOX. MOUNT JUNCTION BOX ABOVE DOOR IN THE CEILING SPACE OF THE SECURE SIDE 120V EM POWER ELECTRIC. FIRE EXIT HARDWARE (EXTERIOR) POWER TRANSFER