Security rough-in and conduit pathways for a door access control system extend from a six-by-six-by-four-inch junction box located above the ceiling. A one-inch conduit runs to the nearest cable tray, while three-quarter-inch conduits feed down to the door frame and the request-to-exit sensor backbox. A one-inch conduit extends down the wall to a four-by-four-by-two-and-one-eighth-inch deep backbox with a single gang ring serving the card reader at forty-eight inches above the floor. Interface coordination is required with Division eight for door hardware and power transfer hinges, and Division twenty-eight for door position switches, request-to-exit sensors, and card readers.
6" 1 2 3 4 A B C 3 2 A B 1 A 4 C 6"x6"X4" JUNCTION BOX ABOVE CEILING FOR DOOR INTERFACE AND POWER 3/4" CONDUIT TO DOOR FRAME 1" CONDUIT TO NEAREST CABLE TRAY 3/4" CONDUIT TO BACK BOX FOR REQUEST-TO-EXIT SENSOR ROUGH-IN FIT-UP DOOR HARDWARE BY DIVISION 8 DOOR POSITION SWITCH BY DIVISION 28 REQUEST-TO-EXIT SENSOR BY DIVISION 28 2 2 5 6 D E E 5 1" CONDUIT DOWN WALL TO CARD READER BACKBOX 6 4"X4"X2-1/8" DEEP BACKBOX WITH SINGLE GANG RING FOR CARD READER D CARD READER BY DIVISION 28 E POWER TRANSFER HINGE BY DIVISION 8 7 SINGLE GANG BACK BOX FLUSH MOUNTED HORIZONTALLY 4" ABOVE CENTER OF DOOR FRAME ON SECURE SIDE OF DOOR FOR REQUEST-TO-EXIT SENSOR 48" 7 CEILING FLOOR NOTE: PATHWAYS REQUIREMENTS SHOWN ARE DIAGRAMMATIC. REFER TO SECURITY SHOP DRAWINGS FOR FINAL PATHWAY REQUIREMENTS CEILING FLOOR NOTE: PATHWAYS REQUIREMENTS SHOWN ARE DIAGRAMMATIC. REFER TO SECURITY SHOP DRAWINGS FOR FINAL PATHWAY REQUIREMENTS