A dry type transformer rests on a four point five inch thick concrete housekeeping pad above the finished floor. The transformer unit is secured at each corner using four three eighths inch diameter expansion anchors with a two and a half inch minimum embedment of minimum SAE one grade. A one half inch thick elastomeric zone sheet is placed at each corner beneath the unit for vibration isolation.
1/2" THICK X REQUIRED SHEET AT CORNER SIZE ELAST. ZORE TRANSFORMER DRY TYPE (4) BOLTS, 3/8" DIA. EXPANSION ANCHORS, 2-1/2" MINIMUM EMBEDMENT. FINISHED FLOOR 4.5" HOUSE KEEPING PAD. (MINIMUN GRADE, SAE1) B A C