An electrical unit rests on a concrete pad with a minimum thickness of six inches, featuring number five reinforcing bars placed at sixteen inches on center each way at mid-height. The pad extends a minimum of four inches on all sides beyond the unit base. Anchors with specified embedment lengths secure the electrical unit into the concrete pad. A minimum three-inch clearance is maintained typically, set above the finished floor.
@ 16" O.C. EA. WAY CONCRETE PAD W/ #5 EMB. LENGTH ANCHOR BY OTHERS ELECTRICAL UNIT 3" MIN. MID. HT. 3" CLR. TYP. 6" THK. MIN. 4" MIN. TYP. ALL SIDES FINISHED FLOOR