Suspended gypsum board ceiling details showing a control joint assembly and a wall slip joint. The control joint incorporates one-and-three-quarter-inch-wide continuous gypsum board strips fastened on one side only over the joint line, supported by one-and-one-half-inch furring channels at four feet on center maximum each way, eight-gauge hanger wires, and eighteen-gauge tie wires with seven-eighths-inch furring channels at twenty-four inches on center maximum. Head screws are spaced at twelve inches on center with a minimum three-eighths-inch clearance from the gypsum board edge. The wall slip joint features a continuous trim angle secured with screws at six inches on center, twelve-gauge hanger wires with a minimum of three turns within one-and-one-half inches, and a metal strut or sixteen-gauge wire to prevent lateral spreading.
8" MAX. 16GA. WIRE TO PREVENT PROVIDE METAL STRUT OR LATERAL SPREADING 12 GA. HANGER WIRE ACOUSTICAL CEILING PANEL WITHIN 1 1/2" (TYP.) MIN. OF 3 TURNS SCREW @ 6" O.C. CONT. TRIM ANGLE 7 SLIP JOINT AT WALL SCALE: N.T.S. RUNNER (SEE NOTE 5) MIN. 3/8" FROM G.B. EDGE HEAD SCREWS @ 12" O.C. 7/8" FURRING CHANNELS @ 24" O.C. MAX. 1 1/2" FURRING CHANNELS @ 4-0" O.C. (1.12 #/FT.) GYP. BD. CLG. WHERE OCCURS @ 4'-0" O.C. MAX EACH WAY 8 GA. HANGER WIRES 18 GA. TIE WIRES 1/2" 3" MAX 1 3/4" WIDE CONTINUOUS RUN OF GYP. BD. STRIPS FASTENED ON ONE SIDE ONLY OVER JOINT LINE 4" MAX. CONTROL JOINT