Partition penetrations for rectangular ducts, pipes, and electrical junction boxes through non-structural metal framing and gypsum board walls. The assembly incorporates acoustic blanket insulation within the stud cavity, partition hangers on each side of the partition, and a maximum half-inch gap between the gypsum board edge and the duct frame opening. Non-rated partitions receive acoustical joint sealant at the perimeter, while fire-rated partitions are sealed with a fire-resistive joint assembly. Electrical junction boxes on opposite sides of the wall are offset by one stud space minimum to maintain acoustical separation.
ACOUSTIC BLANKET INSULATION DUCT 1/2" MAX GAP BETWEEN EDGE OF GYPSUM BOARD AND DUCT FRAME OPENING PARTITION HANGER EACH SIDE OF PARTITION ACOUSTICAL JOINT SEALANT AT NON- RATED PARTITION. PENETRATION FIRE- RESISTIVE JOINT ASSEMBLY AT FIRE- RATED PARTITION ACOUSTIC BLANKET INSULATION PIPE OR DUCT 1/2" MAX GAP BETWEEN EDGE OF GYPSUM BOARD AND PIPE OR DUCT PARTITION HANGER EACH SIDE OF PARTITION ACOUSTICAL JOINT SEALANT AT NON- RATED PARTITION. PENETRATION FIRE- RESISTIVE JOINT ASSEMBLY AT FIRE- RATED PARTITION ACOUSTIC BLANKET INSULATION ACOUSTICAL JOINT SEALANT GYPSUM BOARD NON-STRUCTURAL METAL FRAMING OFFSET JUNCTION BOXES BY ONE STUD SPACE MINIMUM