A hollow structural section tube is enclosed within a UL-U469 one-hour shaftwall assembly. The framing incorporates 2 1/2-inch steel jamb struts and 1-inch shaft liner secured with 1 1/2-inch by 1 1/2-inch 20-gauge minimum clips. A layer of 5/8-inch gypsum board is applied to the exterior framing. An embed or post-applied steel baseplate anchors the assembly per structural requirements.
HSS TUBE - REFER TO STRUCTURAL 1" SHAFT LINER "X" 1" 6 1/4" 6 7/8" 1 1/2" X 1 1/2" 20 GA MIN CLIPS WITH 1" SHAFT LINER UL -U469 1 HOUR SHAFTWALL ASSEMBLY WITH 1 LAYER OF 5/8" GYP BD ON 2 1/2" STL JAMB STRUTS WITH 1" SHAFT LINER UL -U469 1 HOUR SHAFTWALL ASSEMBLY - REFER TO PLANS FOR STUD SIZE EMBED OR POST APPLIED STEEL BASEPLATE - REFERENCE STRUCTURAL