These architectural details show the head-of-wall connection for metal stud partitions beneath concrete slabs and fluted steel decks. A continuous twenty-two gauge minimum three-inch deep leg deflection track is attached to the overhead deck at twelve inches on center maximum. The gypsum board and studs are left unattached to the deflection track in the specified clearance area to accommodate slab movement. A continuous two-inch wide by twenty-two gauge metal strap provides top attachment for the studs at eight inches on center maximum. Mineral wool insulation fills the gap between the slab and the top of the wall, and spray-applied firestop material is applied to each side with a minimum half-inch overlap onto the gypsum board and deck where required.
1" 1" _ FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PARALLEL TO FLUTES DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA SPRAY APPLIED FIRESTOP MATERIAL EACH SIDE - MIN 1/2" OVERLAP AT GYP BD AND DECK CONT 2" WIDE X 22 GA MTL STRAP - ATTACH GYP BD TO STRAP AT 8" OC MAX FILL GAP BETWEEN SLAB AND TOP OF WALL WITH MINERAL WOOL INSULATION CONT 22 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX 1 1/2" 1" _ LINE OF CEILING AS SCHEDULED CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF STUDS CONT 22 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA NON-RATED CONCRETE FLOOR OR ROOF 3/4"