A water cooler unit is mounted to the wall framing using number 10 stainless steel mechanical screws per the manufacturer's recommendations. Vertical heights are dimensioned from the finished floor, maintaining a minimum two feet three inches to maximum three feet zero inches for the lower control, and three feet two inches to three feet six inches for the upper fixture. The installation requires a five-inch maximum typical projection and a minimum fifteen-inch clearance depth for the chiller unit per the manufacturer.
MOUNT FRAME W/#10 SMSS PER MANUFACTURER'S RECOMMENDATIONS FINISH FLOOR FINISH WALL 5" MAX TYP 3'-2" MIN 3'-6" MAX 2'-3" MIN 3'-0" MAX CHILLIER PER MANUFACTURER - PROVIDE 11" MIN CLR DEPTH B SECTION 15" MIN